Vine ST300 Blowing Cold Air on Heat After a Reset? Here’s the Fix for Goodman Heat Pumps

If you reset your Vine ST300 thermostat to reconnect it to the Vine app and now your heat only blows cold air, the thermostat probably isn’t broken. The reset wipes the installer settings.

On a packaged heat pump like the Goodman PHKJ042-1, the wrong reversing valve or stage setting makes the unit cool when you ask for heat.

Why it happens

A heat pump heats and cools with the same outdoor unit. The thermostat tells it which way to run through the O/B wire, which is called the reversing valve. Goodman heat pumps use “O,” which means the valve is energized on Cool. After a factory reset, the ST300 can default to Heat or to two heating stages, and that flips the unit into cooling mode.

The fix (about 2 minutes)

  1. On the thermostat, open Menu, then Setting, then Advanced Setting.
  2. Under Equipment Type, choose Heat Pump and tap Setup.
    Vine ST300 Equipment Type screen with Heat Pump selected and the Setup button showing
    Equipment Type set to Heat Pump — tap Setup to continue.
  3. Set Reversing Valve Energize to Cool.
    Vine ST300 Setup screen on the Heat Pump tab, with Reversing Valve Energize set to Cool and Emergency Heating and Auxiliary Heating set to Disable
    Reversing Valve Energize set to Cool, with emergency and auxiliary heat disabled.
  4. Set Emergency Heating and Auxiliary Heating to Disable, unless you have backup heat strips.
  5. Tap Stage and set Heating Stages to 1 and Cooling Stages to 1.
    Vine ST300 Setup screen on the Stage tab, with Heating Stages set to 1 and Cooling Stages set to 1
    Heating Stages and Cooling Stages both set to 1.
  6. Go back to the main screen, switch the mode to Heat, and set the temperature a few degrees above the room temperature.
  7. Wait 5 to 10 minutes. The compressor has a built-in delay, so warm air won’t come out right away.

These are the working settings we confirmed on a Goodman PHKJ042-1 packaged heat pump:

Vine ST300 working heat settings for a Goodman PHKJ042-1 packaged heat pump: Heat Pump equipment type, reversing valve energized on Cool, and one heating stage

Working Vine ST300 settings for a Goodman packaged heat pump, confirmed after heat was restored.

Still cold?

Try changing Heating Stages to 2 and wait another 5 to 10 minutes. If that doesn’t work, check the wiring. The blue wire (O/B) has to be on the O/B terminal, and the other wires need to match the labels in the app’s wiring screen.